MAXIM Installation Instructions
© Mass Electronics Pty Ltd 2011Chapter 5 – Commissioning
5-2.2.5 TRIAC Outputs
The following items should be checked and verified for proper operation of the TRIAC Outputs on
applicable controllers:
Verify correct polarity of the wiring connected to the TRIAC outputs.
Inspect the controlling device for any defects or problems.
Verify that the current draw for any contactors are within the tolerance of the TRIAC outputs.
Power ON the TRIAC output (force ON using MAXMon).
Check the TRIAC output voltages and verify proper operation of the controlling device
V
AC
V
DC
+
CHECKING ANALOGUE
OUTPUT RESISTANCE
Connected to equipment
or device
2000
Figure 5-5:  Checking Analogue Output Resistance
A TRIAC output cannot be tested without a load applied. Therefore a load of a minimum current rating of 20mA
must be applied for correct operation of the TRIAC outputs.